Fan Performance Evaluation and Efficient System Operation
System Characteristics
The term “system resistance” is used when referring to the static pressure. The system resistance is the sum of static pressure losses in the system. The system resistance is a function of the configuration of ducts, pickups, elbows and the pressure drops across equipment-for example bagfilter or cyclone. The system resistance varies with the square of the volume of air flowing through the system. For a given volume of air, the fan in a system with narrow ducts and multiple short radius elbows is going to have to work harder to overcome a greater system resistance than it would in a system with larger ducts and a minimum number of long radius turns. Long narrow ducts with many bends and twists will require more energy to pull the air through them. Consequently, for a given fan speed, the fan will be able to pull less air through this system than through a short system with no elbows. Thus, the system resistance increases substantially as the volume of air flowing through the system increases; square of air flow.
Conversely, resistance decreases as flow decreases. To determine what volume the fan will produce, it is therefore necessary to know the system resistance characteristics.
In existing systems, the system resistance can be measured. In systems that have been designed, but not built, the system resistance must be calculated. Typically a system resistance curve is generated with for various flow rates on the x-axis and the associated resistance on the y-axis
Fan Characteristics
Fan characteristics can be represented in form of fan curve(s). The fan curve is a performance curve for the particular fan under a specific set of conditions. The fan curve is a graphical representation of a number of inter-related parameters. Typically a curve will be developed for a given set of conditions usually including: fan volume, system static pressure, fan speed, and brake horsepower required to drive the fan under the stated conditions. Some fan curves will also include an efficiency curve so that a system designer will know where on that curve the fan will be operating under the chosen conditions (see Figure 5.6). In the many curves shown in the Figure, the curve static pressure (SP) vs. flow is especially important.
The intersection of the system curve and the static pressure curve defines the operating point. When the system resistance changes, the operating point also changes. Once the operating point is fixed, the power required could be found by following a vertical line that passes through the operating point to an intersection with the power (BHP) curve. A horizontal line drawn through the intersection with the power curve will lead to the required power on the right vertical axis. In the depicted curves, the fan efficiency curve is also presented.
System Characteristics and Fan Curves
In any fan system, the resistance to air flow (pressure) increases when the flow of air is increased. As mentioned before, it varies as the square of the flow. The pressure required by a system over a range of flows can be determined and a "system performance curve" can be developed (shown as SC) (see Figure 5.7).
This system curve can then be plotted on the fan curve to show the fan's actual operating point at "A" where the two curves (N1 and SC1) intersect. This operating point is at air flow Q1 delivered against pressure P1.
Figure 5.6 Fan Characteristics Curve by Manufacturer
A fan operates along a performance given by the manufacturer for a particular fan speed. (The fan performance chart shows performance curves for a series of fan speeds.) At fan speed N1, the fan will operate along the N1 performance curve as shown in Figure 5.7. The fan's actual operating point on this curve will depend on the system resistance; fan’s operating point at “A” is flow (Q1) against pressure (P1).
Two methods can be used to reduce air flow from Q1 to Q2:
First method is to restrict the air flow by partially closing a damper in the system. This action causes a new system performance curve (SC2) where the required pressure is greater for any given air flow. The fan will now operate at "B" to provide the reduced air flow Q2 against higher pressure P2.
Second method to reduce air flow is by reducing the speed from N1 to N2, keeping the damper fully open. The fan would operate at "C" to provide the same Q2 air flow, but at a lower pressure P3.
Thus, reducing the fan speed is a much more efficient method to decrease airflow since less power is required and less energy is consumed.
Fan Laws
The fans operate under a predictable set of laws concerning speed, power and pressure. A change in speed (RPM) of any fan will predictably change the pressure rise and power necessary to operate it at the new RPM.
Fan Design and Selection Criteria
Precise determination of air-flow and required outlet pressure are most important in proper selection of fan type and size. The air-flow required depends on the process requirements; normally determined from heat transfer rates, or combustion air or flue gas quantity to be handled. System pressure requirement is usually more difficult to compute or predict. Detailed analysis should be carried out to determine pressure drop across the length, bends, contractions and expansions in the ducting system, pressure drop across filters, drop in branch lines, etc. These pressure drops should be added to any fixed pressure required by the process (in the case of ventilation fans there is no fixed pressure requirement). Frequently, a very conservative approach is adopted allocating large safety margins, resulting in over-sized fans which operate at flow rates much below their design values and, consequently, at very poor efficiency.
Once the system flow and pressure requirements are determined, the fan and impeller type are then selected. For best results, values should be obtained from the manufacturer for specific fans and impellers.
The choice of fan type for a given application depends on the magnitudes of required flow and static pressure. For a given fan type, the selection of the appropriate impeller depends additionally on rotational speed. Speed of operation varies with the application. High speed small units are generally more economical because of their higher hydraulic efficiency and relatively low cost. However, at low pressure ratios, large, low-speed units are preferable.
Fan Performance and Efficiency
In the case of centrifugal fans, the hub-to-tip ratios (ratio of inner-to- outer impeller diameter) the tip angles (angle at which forward or backward curved blades are curved at the blade tip - at the base the blades are always oriented in the direction of flow), and the blade width determine the pressure developed by the fan.
Forward curved fans have large hub-to-tip ratios compared to backward curved fans and produce lower pressure.
Radial fans can be made with different heel-to-tip ratios to produce different pressures.
At both design and off-design points, backward-curved fans provide the most stable operation. Also, the power required by most backward –curved fans will decrease at flow higher than design values. A similar effect can be obtained by using inlet guide vanes instead of replacing the impeller with different tip angles. Radial fans are simple in construction and are preferable for high-pressure applications.
Forward curved fans, however, are less efficient than backward curved fans and power rises continuously with flow. Thus, they are generally more expensive to operate despite their lower first cost. Among centrifugal fan designs, aerofoil designs provide the highest efficiency (upto 10% higher than backward curved blades), but their use is limited to clean, dust-free air.
Axial-flow fans produce lower pressure than centrifugal fans, and exhibit a dip in pressure before reaching the peak pressure point. Axial-flow fans equipped with adjustable / variable pitch blades are also available to meet varying flow requirements.
Propeller-type fans are capable of high-flow rates at low pressures. Tube-axial fans have medium pressure, high flow capability and are not equipped with guide vanes.Vane-axial fans are equipped with inlet or outlet guide vanes, and are characterized by high pressure, medium flow-rate capabilities.
Performance is also dependant on the fan enclosure and duct design. Spiral housing designs with inducers, diffusers are more efficient as compared to square housings. Density of inlet air is another important consideration, since it affects both volume flow-rate and capacity of the fan to develop pressure. Inlet and outlet conditions (whirl and turbulence created by grills, dampers, etc.) can significantly alter fan performance curves from that provided by the manufacturer (which are developed under controlled conditions). Bends and elbows in the inlet or outlet ducting can change the velocity of air, thereby changing fan characteristics (the pressure drop in these elements is attributed to the system resistance). All these factors, termed as System Effect Factors, should, therefore, be carefully evaluated during fan selection since they would modify the fan performance curve.
Centrifugal fans are suitable for low to moderate flow at high pressures, while axial-flow fans are suitable for low to high flows at low pressures. Centrifugal fans are generally more expensive than axial fans. Fan prices vary widely based on the impeller type and the mounting (direct-or- belt-coupled, wall-or-duct-mounted). Among centrifugal fans, aerofoil and backward-curved blade designs tend to be somewhat more expensive than forward-curved blade designs and will typically provide more favourable economics on a lifecycle basis. Reliable cost comparisons are difficult since costs vary with a number of application-specific factors. A careful technical and economic evaluation of available options is important in identifying the fan that will minimize lifecycle costs in any specific application.
www.bilkargroup.com
www.bilkarsogutma.com.tr
info@bilkargroup.com
+90 212 343 50 40
+90 553 343 50 40
Hiç yorum yok:
Yorum Gönder